Balancing instrument, PFM-2000

 

A precision instrument for the measuring and documentation of water flow in heating, cooling and drinking water systems.

PFM-2000 is a meter for pressure and flow measurements across, for example, balancing valves. Valve characteristics for a number of valves from different manufactures are stored in the PFM-2000’s memory. The valvedatabase is updated continuously. Every instrument unit is delivered with a CD-ROM containing demo programs, valve data and manuals.

 

Technical specifications    
       
Measurin range   Accuracy  
Pressure difference: up to 150 kPa Pressure difference: < 10 kPa +/- 0.1 kPa
  at total pressure < 1000 kPa   > 10kPa +/- 1% of metered value
  Max 2000 kPa Flow: As for  pressure + the valve's deviation
Static pressure: up to 1000 kPa    
    Environment  
Resolution   Temperature, media: -10o C to 100o C
Pressure difference: 0,01 kPa, at total pressure < 100 kPa Temperature, storage: -20o C to +60o C
  0,1 kPa, at total pressure > 100 kPa Humidity, not controlled: Max 90% RH
Static pressure: 10 kPa    
Flow: 0,001 l/s Power supply  
    Capacity: 1500 mAh
    R6 rechargeable NiMH-batteries (6)  
       
Included in delivery

Meter x1
Sensor x1
Cable x1
Hoses & connectors x2
Battery charger x1
Strong carrying case x1
Allen key, 3 mm, x1
Allen key, 5 mm, x1
Manual x1
Program diskette x1
Calibration protocol, x1